The following is an overview of the user manual for the Z-Wave product Multireg Z-Wave (TF016)from Thermo-Floor AS. To view other Z-Wave products and manuals from Thermo-Floor AS follow that link.
Overview
The display will show the actual room temperature.
By pressing the buttons, the display will show the set value.
Heatit Z-Wave is equipped with a single-pole switch. The thermostat can handle loads up to 16A/3600W at 230V.
If the load is greater than this, the thermostat needs to be connected to a contactor. It can be used with two external temperature sensors.
Functions:
• Room sensor
• Floor sensor
• Temperature limiter
• Power regulator
• Z-Wave chip 500 series
• Week program/setback temperature via gateway
• Setback mode
• 7-segment white LCD-screen
• Can be used in connection with different NTC-sensors
• Lock mode/child lock
• Backlight
• Calibration
• 8 scenarios
CONNECTION CLAMPS
Use 1,5 mm² or 2,5 mm² cables according to power need.
TECHNICAL DATA
Rated voltage: 230 V 50/60 Hz
Max. load: 3600W
Max. current: 16A
Power consumption: 1,5W
Protection class: IP21
Min/Max installation temp: -20°C to 40°C
Min/Max operating temp: 5°C to 40°C
Temperature intervals: Floor sensor 5°C to 40°C
Room sensor 5°C to 40°C
Hysteresis: 0,5°C
Sensor values: 0°C 29,1 kOhm
10°C 18,6 kOhm
15°C 15,1 kOhm
20°C 12,2 kOhm
25°C 10,0 kOhm
Breaker: Single-pole
Security
As a Z-Wave Plus certified product, Multireg Z-Wave supports Z-Wave S2 security. The following security modes are directly supported:
Features
Thermo-Floor AS describes Multireg Z-Wave as having the following features:
- FLiRS capable
- Supports Network Wide Inclusion
- Supports Z-Wave Explorer Frames
- Supports Z-Wave SmartStart allowing you to setup the product simply by scanning its QR code via
Installation instructions
Inclusion/exclusion mode
To include the thermostat to your home automation gateway, press the Center (confirm) button for 10 seconds.
The display will show OFF. Press Right (down) button 4 times till you see Con in the display.
Now start adding device in your home automation software.
Start inclusion mode by pressing Center (confirm) button for approximately 2 seconds. The inclusion/exclusion icon will appear in the display.
Confirmation will show Inc/EcL in the display.
If inclusion fails, Err (error) will appear.
Inclusion/exclusion mode
To include the thermostat to your home automation gateway, press the Center (confirm) button for 10 seconds.
The display will show OFF. Press Right (down) button 4 times till you see Con in the display.
Now start adding device in your home automation software.
Start inclusion mode by pressing Center (confirm) button for approximately 2 seconds. The inclusion/exclusion icon will appear in the display.
Confirmation will show Inc/EcL in the display.
If inclusion fails, Err (error) will appear.
If Er2 appears in the display, touch any button to restart the display.
Factory reset Multireg Z-Wave
Factory reset - RES:
By pressing buttons Left and Center(up and confirm) for 20 seconds, the thermostat will perform a complete factory reset.
NB! Please use this procedure only when the primary controller is missing or otherwise inoperable.
Please note that this is a user manual Multireg Z-Wave from Thermo-Floor AS is provided as is and without warranty; all information contained herein is provided by the manufacturer or the certifying body. The information provided is for reference only and is not intended to be used as a substitute for professional advice. ZWaveProducts.com only warrants and is only able to support products purchased directly from us. If you have Multireg Z-Wave and have not purchased it from us, please contact the manufacturer directly with any further questions you may have.